Payment Terms | T/T |
Supply Ability | 1piece in stock |
Delivery Time | 3 day |
Packaging Details | 150*50*50mm |
Probe length L[mm] | 45 |
Weight[g] | 257 |
Dimensions[mm] | Ø 34 / L = 142 |
Brand Name | IFM |
Model Number | SA5000 |
Certification | 3C |
Place of Origin | GERMANY |
View Detail Information
Explore similar products
IFM Inductive Full-metal Sensor II502A IIK3010-BPKG/AM/US104DPS/3G/3D Connector
Inductive Sensor IIS206 IIKC015BASKG/2LED Flush Mountable Connector 1 X M12
IIS238 Inductive Sensor IfmElectronic For Industrial Mobile Cooling And
IFM Electronic Gmbh Inductive Sensor IM0010 Non-flush Mountable
Product Specification
Payment Terms | T/T | Supply Ability | 1piece in stock |
Delivery Time | 3 day | Packaging Details | 150*50*50mm |
Probe length L[mm] | 45 | Weight[g] | 257 |
Dimensions[mm] | Ø 34 / L = 142 | Brand Name | IFM |
Model Number | SA5000 | Certification | 3C |
Place of Origin | GERMANY | ||
High Light | IFM SA5000 flow sensor ,IFM pressure sensor with warranty ,SA5000 industrial flow sensor |
Product characteristics | |||||||||||
Number of inputs and outputs Number of digital outputs: 2; Number of analogue outputs: 1 Process connection threaded connection M18 x 1,5 internal thread | |||||||||||
Application | |||||||||||
Special feature | Gold-plated contacts | ||||||||||
Media | water; glycol solutions; air; oils | ||||||||||
Note on media | low-viscosity oils with viscosity: ≤ 40 mm²/s (40 °C) | ||||||||||
high-viscosity oils with viscosity: > 40 mm²/s (40 °C) | |||||||||||
Medium temperature | [°C] | -20...90 | |||||||||
Pressure rating | [bar] | 100 | |||||||||
Pressure rating | [Mpa] | 10 | |||||||||
MAWP (for applications according to CRN) | [bar] | 100 | |||||||||
![]() | |||||||||||
SA5000 | |||||||||||
Flow sensor | |||||||||||
SAD10XDBFRKG/US-100 | |||||||||||
Electrical data | |||||||||||
Operating voltage | [V] | 18...30 DC | |||||||||
Current consumption | [mA] | < 100 | |||||||||
Protection class | III | ||||||||||
Reverse polarity protection | yes | ||||||||||
Power-on delay time | [s] | 10 | |||||||||
Inputs / outputs | |||||||||||
Number of inputs and outputs | Number of digital outputs: 2; Number of analogue outputs: 1 | ||||||||||
Outputs | |||||||||||
Total number of outputs | 2 | ||||||||||
Output signal | switching signal; analogue signal; frequency signal; IO-Link; (configurable) | ||||||||||
Electrical design | PNP/NPN | ||||||||||
Number of digital outputs | 2 | ||||||||||
Output function | normally open / normally closed; (parameterisable) | ||||||||||
Max. voltage drop switching output DC | [V] | 2.5 | |||||||||
Permanent current rating of switching output DC | [mA] | 250 | |||||||||
Number of analogue outputs | 1 | ||||||||||
Analogue current output | [mA] | 4...20; (scalable) | |||||||||
Max. load | [Ω] | 350 | |||||||||
Short-circuit protection | yes | ||||||||||
Type of short-circuit protection | pulsed | ||||||||||
Overload protection | yes | ||||||||||
Frequency of the output [Hz] | 0...1000 | ||||||||||
Measuring/setting range | |||||||||||
Probe length L | [mm] | 45 | |||||||||
Operating mode | relative; absolutely liquid; absolutely gaseous; (absolute: reference measurement recommended) | ||||||||||
Note on factory setting | Operating mode: relative | ||||||||||
Liquids | |||||||||||
Setting range Greatest sensitivity | [m/s] [m/s] | 0.04...6 0.04...3 | |||||||||
Gases | |||||||||||
Setting range Greatest sensitivity | [m/s] [m/s] | 0...200 2...100 | |||||||||
Temperature monitoring | |||||||||||
Measuring range Resolution | [°C] [°C] | -20...90 0.2 | |||||||||
![]() | |||||||||||
SA5000 | |||||||||||
Flow sensor | |||||||||||
SAD10XDBFRKG/US-100 | |||||||||||
Accuracy / deviations Flow monitoring | |||||||||||
Temperature drift | [cm/s x 1/K] | 0,003 m/s x 1/K (< 20 °C; > 70 °C) | |||||||||
Temperature gradient [K/min] | 100 | ||||||||||
Accuracy | ± (7 % MW + 2 % MEW); (for relative mode in the range of maximum sensitivity under the following conditions:; water: 20...70 °C; inlet length: 1.5 m; DN25 (DIN 2448); mounting position according to instructions; Accuracy can differ for other media and mounting positions.) | ||||||||||
Repeatability | 0,05 m/s; (water; flow velocity: 0,05...3 m/s) | ||||||||||
Temperature monitoring | |||||||||||
Temperature drift ± 0,005 K/°C Accuracy [K] ± 0,3 / ± 1; (water; flow velocity: 0,3...3 m/s / air; flow velocity: > 10 m/s) | |||||||||||
Response times Flow monitoring | |||||||||||
Response time [s] | 0.5; (T09; water; glycol: 0,8 s; air: 7 s; oil: 1,8 s; each T09) | ||||||||||
Temperature monitoring | |||||||||||
Dynamic response T05 / T09 [s] | 1,5 (T09); (water; flow velocity: 0,3...3 m/s) | ||||||||||
Software / programming | |||||||||||
Parameter setting options | hysteresis / window; normally open / normally closed; switching logic; current/ frequency output; medium selection; Damping; Teach function; display can be rotated and switched off; standard unit of measurement; process value colour | ||||||||||
Interfaces | |||||||||||
Communication interface | IO-Link | ||||||||||
Transmission type | COM2 (38,4 kBaud) | ||||||||||
IO-Link revision | 1.1 | ||||||||||
SDCI standard | IEC 61131-9 | ||||||||||
Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis | ||||||||||
SIO mode | yes | ||||||||||
Required master port type | A | ||||||||||
Process data analogue | 2 | ||||||||||
Process data binary | 2 | ||||||||||
Min. process cycle time [ms] | 3 | ||||||||||
Supported DeviceIDs | Type of operation | DeviceID | |||||||||
Factory setting / ModE = (REL) | 533 | ||||||||||
ModE = (LIQU) | 540 | ||||||||||
ModE = (GAS) | 547 | ||||||||||
Operating conditions | |||||||||||
Ambient temperature [°C] | -40...80 | ||||||||||
Storage temperature Protection | [°C] | -40...100 IP 65; IP 67 | |||||||||
![]() | |||||||||||
SA5000 | |||||||||||
Flow sensor | |||||||||||
SAD10XDBFRKG/US-100 | |||||||||||
Tests / approvals | |||||||||||
EMC | DIN EN 60947-5-9 | ||||||||||
Shock resistance | DIN EN 60068-2-27 | 50 g (11 ms) | |||||||||
Vibration resistance | DIN EN 60068-2-6 | 20 g (10...2000 Hz) | |||||||||
MTTF [years] | 132 | ||||||||||
UL approval | UL Approval no. | I003 | |||||||||
Mechanical data | |||||||||||
Weight [g] | 314 | ||||||||||
Materials | stainless steel (1.4404 / 316L); stainless steel (1.4310 / 301); PBT-GF20; PBT-GF30 | ||||||||||
Materials (wetted parts) Process connection | stainless steel (1.4404 / 316L); Gasket: FKM threaded connection M18 x 1,5 internal thread | ||||||||||
Displays / operating elements | |||||||||||
Display unit | 6 x LED, green (%, m/s, l/min, m³/h, °C, 10³) | ||||||||||
Display | switching status | 2 x LED, yellow | |||||||||
measured values | alphanumeric display, red/green 4-digit | ||||||||||
Remarks | |||||||||||
Remarks | MW = measured value | ||||||||||
MEW = Final value of the measuring range | |||||||||||
Pack quantity | 1 pcs. |
Company Details
Business Type:
Trading Company
Year Established:
2017
Total Annual:
300000-800000
Employee Number:
12~20
Ecer Certification:
Verified Supplier
Xiamen Zhicheng Automation Technology Co., Ltd Xiamen Zhicheng Automation Technology Co., Ltd. Still Working And Able To Shipping Worldwide.We Are The Supplier For Industrial Automation Spare Parts.we Specialize In Plc Module, Dcs Card Pieces, Esd System C... Xiamen Zhicheng Automation Technology Co., Ltd Xiamen Zhicheng Automation Technology Co., Ltd. Still Working And Able To Shipping Worldwide.We Are The Supplier For Industrial Automation Spare Parts.we Specialize In Plc Module, Dcs Card Pieces, Esd System C...
Get in touch with us