Payment Terms | T/T, L/C |
Supply Ability | 30pcs/month |
Delivery Time | 3-5days |
Packaging Details | new in box |
Description | X20 Module Opensafety Manager For Up To 100 Safenodes |
Warranty | 1year |
Interfaces | POWERLINK |
System module | CPU |
B&R ID code | 0xDD61 |
Power consumption | 4.3 W |
Input voltage | 24 VDC -15% / +20% |
Input current | Max. 0.25 A |
Weight | 190 g |
Brand Name | B&R |
Model Number | X20SL8100 |
Place of Origin | Austria |
View Detail Information
Explore similar products
X20CP1586 | B&R | X20 CPU ATOM System module Controller
X20CM0985 | B&R | Analog inputs X20 energy measurement and synchronization
X20CP1583 B&R PLC Module Industrial Fanless Cooling with B R ID code 0xD45B
8SCS000.0000-00 B&R Shield.comp.set 1xSCHBL 1xSCH ACOPOSmulti shield component
Product Specification
Payment Terms | T/T, L/C | Supply Ability | 30pcs/month |
Delivery Time | 3-5days | Packaging Details | new in box |
Description | X20 Module Opensafety Manager For Up To 100 Safenodes | Warranty | 1year |
Interfaces | POWERLINK | System module | CPU |
B&R ID code | 0xDD61 | Power consumption | 4.3 W |
Input voltage | 24 VDC -15% / +20% | Input current | Max. 0.25 A |
Weight | 190 g | Brand Name | B&R |
Model Number | X20SL8100 | Place of Origin | Austria |
High Light | X20SL8100 ,X20SL8100 B&R PLC Module |
Product Description
Material number:
X20SL8100
Description:
openSAFETY manager for up to 100 SafeNODEs
Flexibly programmable using Automation Studio / SafeDESIGNER
Innovative management of safe machine options (SafeOPTION)
Parameter and configuration management
The module is equipped with SafeLOGIC functionality that allows it to safely execute applications designed in SafeDESIGNER. The module can be used in safety-related applications up to PL e or SIL 3.
In addition, the module coordinates the safety-related communication of all modules involved in the application. In this context, the module also monitors the configuration of these modules and carries out autonomous parameter downloads to the modules whenever necessary. This guarantees a consistent and correct module configuration in the network from a safety standpoint in all scenarios involving module replacement and service. These services are performed by the SafeLOGIC controller.
Product Information
Short description
Interfaces | POWERLINK |
System module | CPU |
General information
B&R ID code | 0xDD61 |
System requirements |
|
Automation Studio | 4.0.16 or later |
Automation Runtime | V3.08 or later (for AsSafety library F4.06 or later) |
SafeDESIGNER | 3.1.0 or later |
Safety Release | 1.7 or later |
mapp Technology Package | mapp Safety 5.7.0 or later |
Cooling | Fanless |
Status indicators | CPU function, POWERLINK, SafeKEY |
Diagnostics |
|
CPU function | Yes, using LED status indicator |
POWERLINK | Yes, using LED status indicator |
SafeKEY | Yes, using LED status indicator |
Support |
|
Dynamic node allocation (DNA) | Yes |
Power consumption | 4.3 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications |
|
CE | Yes |
UKCA | Yes |
Functional safety | cULus FSPC E361559 |
Functional safety | IEC 61508:2010, SIL 3 |
Functional safety | EN 50156-1:2004 |
ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc |
UL | cULus E115267 |
HazLoc | cCSAus 244665 |
DNV | Temperature: A(0 to 45°C) |
CCS | Yes |
LR | ENV1 |
KR | Yes |
ABS | Yes |
BV | EC21B |
Safety characteristics
EN ISO 13849-1:2015 |
|
Category | Cat. 4 |
PL | PL e |
DC | >94% |
MTTFD per channel | 2500 years |
Mission time | Max. 20 years |
IEC 61508:2010, |
|
SIL CL | SIL 3 |
SFF | >90% |
PFH / PFHd per channel | <1*10-10 |
PFH / PFHd |
|
openSAFETY wired | Negligible |
openSAFETY wireless | <1*10-14* Number of openSAFETY packets per hour |
PFD per channel | <2*10-5 |
Proof test interval (PT) | 20 years |
Functionality
Communication with each other | Yes |
Support for Safe Commissioning Options |
|
BOOL | 512 |
INT | 64 |
UINT | 64 |
DINT | 64 |
UDINT | 64 |
SafeMOTION support | Yes, depends on the number of available operating licenses on the SafeKEY |
Max. number of SafeMOTION axes | 70, depends on the data width of the modules used |
Timing precision | Time * 0.05 + Cycle time of the safety application |
Shortest task class cycle time | 1 ms |
Max. number of SafeNODEs | 100, depends on the number of available operating licenses on the SafeKEY |
Max. number of POWERLINK controlled nodes | 50 |
Data exchange between CPU and SafeLOGIC controller |
|
Max. total data width for each direction | 512 bytes |
Max. number of data points for each direction |
|
BOOL | 1024 |
INT | 128 |
UINT | 128 |
DINT | 64 |
UDINT | 64 |
Data exchange between SafeDOMAIN and SafeDOMAIN |
|
Use as Managing SafeDOMAIN | Yes, starting with mapp Safety 5.10.0 and hardware upgrade 2.2.1.0 |
Use as Connected SafeDOMAIN | Yes, starting with mapp Safety 5.10.0 and hardware upgrade 2.2.1.0 |
Max. total data width for each direction | 64 bytes |
Max. total number of data points for each direction | 16 |
Max. number of data points for each direction |
|
BOOL | 128 |
INT | 16 |
UINT | 16 |
DINT | 16 |
UDINT | 16 |
Max. number of linked Managing SafeDOMAINs | Starting with mapp Safety 5.10.0 and hardware upgrade 2.2.1.0: 10 |
Limit values for SafeDESIGNER application
Max. resources available for SafeDESIGNER info window entries |
|
FB instances | 4096 |
Marker memory | 262,144 bytes |
Stack memory | 32,768 bytes |
Memory for safe input data | 6144 bytes |
Memory for safe output data | 2048 bytes |
Memory for standard input data | 1024 bytes |
Memory for standard output data | 1024 bytes |
Marker count | 16,382 |
Additional SafeDESIGNER limit values |
|
Max. number of function block types | 512 |
Max. number of force variables | 64 |
Max. number of variable with variable status | 1023 |
Input SL / BC / X2X Link power supply
Input voltage | 24 VDC -15% / +20% |
Input current | Max. 0.25 A |
Fuse | - |
Reverse polarity protection | Yes |
Interfaces
Fieldbus | POWERLINK controlled node |
Variant | 2x shielded RJ45 port (hub) |
Line length | Max. 100 m between 2 nodes (segment length) |
Transfer rate | 100 Mbit/s |
Transfer |
|
Physical layer | 100BASE-TX |
Half-duplex | Yes |
Full-duplex | No |
Autonegotiation | Yes |
Auto-MDI/MDIX | Yes |
Min. cycle time |
|
Fieldbus | 200 µs |
Operating conditions
Mounting orientation |
|
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | 0 to 2000 m, no limitation |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature |
|
Operation |
|
Horizontal mounting orientation | 0 to 60°C |
Vertical mounting orientation | 0 to 45°C |
Derating | - |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity |
|
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note | Order SafeKEY and SafeLOGIC range of functions using the X20MK configurator. |
Dimensions |
|
Width | 62.5+0.2mm |
Height | 99 mm |
Depth | 75 mm |
Weight | 190 g |
Product Photo
More Products
X20PS9600 | X20SO6300 | X20DC4395 |
X20CP0483 | X20SLX210 | X20BT9100 |
X20CP1483 | X20DI4371 | X20DI9371 |
x20cp1586 | X20BM05 | X20AT6402 |
X20CP1583 | X20BC0083 | X20AI4622 |
X20CP3584 | X20BC8083 | x20at4222 |
X20CP3583 | X20BB80 | x20bt9400 |
X20CP1585 | X20BM11 | X20AT2222 |
X20CP1584 | X20TB12 | X20AO4622 |
X20CP1684 | X20IF1072 | X20DO9322 |
X20CP1382 | X20DO6322 | X20IF1030 |
X20AI1744 | X20DC2395 | X20IF1082-2 |
X20DI6371 | X20BM15 | X20IF371 |
X20DOF322 | X20DO4332 | X20CM4810 |
X20DS4389 | X20DO4322 | X20AI83211 |
X20PS2100 | X20MM2436 | X20DOF322 |
X20PS9400 | X20DO8332 | X20PS3330 |
X20CS1030 | X20DC11A6 | X20BM01 |
X20CS1020 | X20CM8281 | X20SI9100 |
X20ATC402 | X20BR9300 | X20SI4100 |
Cooperative Brand
(DCS)
ABB / TRICONEX / FOXBORO/ I/A / HONEYWELL / TDC2000/3000 / YOKOGAWA / BENTLY NEVADA
(PLC)
B&R / ALLEN BRADLEY / BECKHOFF / HONEYWELL / OMRON / SIEMENS
(SENSOR)
IFM / SICK/ P+F/ WENGLOR / BAUMER / LEUZE / HOLLY/ SYSHOKUYO / EUCHNER
(CONNECTOR)
HARTING / PHOENIX CONTACT/ WEIDMUELLER
(VALVE)
SMC / FESTO / +GF+.......
(INSTRUMENT)
+GF+ /E+H / HITACHI / ROSEMOUNT
Why Choose Us
Xiamen ZhiCheng Automation Technology Co., Ltd it is a leading global supplier of control system components. We specialize in control systems and drives. With many years of experience in the industrial sector, we consistently deliver the highest quality of spare parts. We have tens of thousands of spare partsand spare parts warehouse . Products and services to serve for installing of users control system,Distributed control systems, programmable controllers, panel controller and drive!
We major in DCS system,Sensor,PLC,Connector,Valve, and Instrument,MAGNETRON,RO Membrane. With many years of experience in the industrial sector, we consistently deliver the highest quality of spare parts.which make sure that all this jobs are perfectly. If you have any further questions, please don't hesitate to contact us.
How To Contact Me
Company Details
Business Type:
Trading Company
Year Established:
2017
Total Annual:
300000-800000
Employee Number:
12~20
Ecer Certification:
Verified Supplier
Xiamen Zhicheng Automation Technology Co., Ltd Xiamen Zhicheng Automation Technology Co., Ltd. Still Working And Able To Shipping Worldwide.We Are The Supplier For Industrial Automation Spare Parts.we Specialize In Plc Module, Dcs Card Pieces, Esd System C... Xiamen Zhicheng Automation Technology Co., Ltd Xiamen Zhicheng Automation Technology Co., Ltd. Still Working And Able To Shipping Worldwide.We Are The Supplier For Industrial Automation Spare Parts.we Specialize In Plc Module, Dcs Card Pieces, Esd System C...
Get in touch with us
Leave a Message, we will call you back quickly!